Hager RCD/MCB Switch ADX416D

Manufacturer: Hager
Designation: 4-pole RCD/MCB, 10kA
Type: ADX416D
Number of Poles (total): 4
Number of Protected Poles: 4
Rated Voltage: 400 V
Rated Insulation Voltage Ui: 500 V
Rated Impulse Voltage Withstand Uimp: 4 kV
Rated Current: 16 A
Rated Residual Current: 0.03 A
Residual Current Type: A
Energy Limitation Class: 3
Power Loss: 10.9 W
Rated Tripping Capacity according to IEC 60947-2: 10 kA
Rated Switching Capacity Icn according to EN 61009-1: 10 kA
Tripping Characteristic: instantaneous
Surge Current Withstand: 3 kA
Type of Voltage: AC
Frequency: 50 Hz
Tripping Characteristic: B
Switching Neutral Conductor: yes
With Locking Mechanism: yes
Overvoltage Category: 3
Degree of Pollution: 2
Ambient Temperature during Operation: -25..40 °C
Width in Division Units: 4
Installation Depth: 70 mm
Flush Mounting: yes
False Tripping Protection: no
Protection Class (IP): IP2X
Connectable Conductor Cross-Section Solid: 1..25 mm²
Connectable Conductor Cross-Section Stranded: 1..16 mm²

Hager RCD/MCB Switch ADX416D: additional details
Residual Current Circuit Breaker 4P 10kA B-16A 30mA Type A. Residual current circuit breaker according to DIN EN 61009-1 (VDE 0664-20) with a 4-pole circuit breaker for 400 V three-phase circuits and a residual current protection circuit in a compact housing, blue test button, and residual current indicator. Easy single removal from the phase rail connection. Suitable for retrofitting additional devices. Labeling option directly on the device.

Key specifications

Circuit breaker type
Residual current protection block
Mounting type
Flush-mounted
number of poles
4
Length
70 mm
Width
71 mm

General information

Item number
20762521
Manufacturer
Hager
Category
Residual-current device
Manufacturer no.
ADX416D
Release date
4.5.2022
Sales rank in Category Residual-current device
83 of 16736
External links

Circuit Breaker Features

Circuit breaker type
Residual current protection block
Mounting type
Flush-mounted
number of poles
4
Tripping characteristic
B
Rated current
16 A
Rated current
0.03 A
Rated voltage
400 V
voltage type
AC
Rated insulation voltage Ui
500 V
Residual current (rated differential current)
0.03 A
Protection type (IP code)
IPX2

Origin

Country of origin
China

Voluntary climate contribution

CO₂ emissions
22.53 kg
Climate contribution
CHF 0.54

Scope of delivery

Items per sales unit
1 pcs.

Product dimensions

Length
70 mm
Width
71 mm
Height
84 mm

Package dimensions

Length
8 cm
Width
10 cm
Height
7 cm
Weight
430 g

30-day right of return
24 Months Warranty (Bring-in)
3 additional offers

Compare products

Goes with

Reviews & Ratings

Warranty score

How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?

Source: Digitec Galaxus
  • 1.Schneider Electric
    0 %
  • 1.Siemens
    0 %
  • 5.ABB
    0.1 %
  • 6.Hager
    0.2 %
  • 7.Steffen
    0.4 %

Warranty case duration

How many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?

Source: Digitec Galaxus
  • Hager
    Not enough data
  • ABB
    Not enough data
  • Brennenstuhl
    Not enough data
  • Eaton
    Not enough data
  • Max Hauri
    Not enough data

Unfortunately, we don't have enough data for this category yet.

Return rate

How often is a product of this brand in the «Residual-current device» category returned?

Source: Digitec Galaxus
  • 3.Schneider Electric
    1.5 %
  • 4.ABB
    2.1 %
  • 5.Max Hauri
    3.8 %
  • 5.Siemens
    3.8 %
  • 7.Hager
    5.3 %
Source: Digitec Galaxus