Gewiss Ground fault circuit interrupter
More than 10 pieces in stock at supplier
number of poles2
Rated current3
Residual current (rated differential current)2
Product details
Gewiss residual current circuit breaker GWD4132
Manufacturer: Gewiss
Designation: Residual current circuit breaker 4-p, 40A, 30mA
Type: GWD4132
Number of poles: 4
Rated voltage: 400 V
Rated current: 40 A
Rated residual current: 0.03 A
Rated insulation voltage Ui: 500 V
Rated impulse voltage resistance Uimp: 4 kV
Power loss: 11.7 W
Mounting type: DIN rail
Residual current type: A
Selective type: No
Short time delayed type: No
Short-circuit strength (Icw): 10 kA
Surge current strength: 0.25 kA
Voltage type: AC
With locking device: No
Frequency: 50/60 Hz
Additional devices possible: Yes
Protection class (IP): IP20
Width in division units: 4
Installation depth: 72 mm
Ambient temperature during operation: -25 to 40 °C
Degree of pollution: 2
Connectable conductor cross-section multi-wire: 35 mm²
Connectable conductor cross-section single-wire: 35 mm²
Explosion protected: No
The residual current circuit breaker is a network voltage-independent residual current device (RCCB) according to EN61008-1. It is suitable for retrofitting 2 additional devices and/or combinations with modules for automatic reset (restart). The switch lever can be sealed in both the ON and OFF positions or locked with a lever lock (accessory to be ordered separately) for a padlock.
It features an integrated residual current indicator and a foldable labeling plate. Connection (max): 35 mm² with insulated plug-in protection. The connection screws can be equipped with a sealable cover (accessory to be ordered separately).
EAN: 8011564824294.
Circuit breaker type | Fault current circuit breaker |
Mounting type | Top-hat rail |
number of poles | 4 |
Length | 72 mm |
Item number | 23047917 |
Manufacturer | Gewiss |
Category | Residual-current device |
Manufacturer No. | GWD4132 |
Release date | 9.11.2022 |
External links |
Circuit breaker type | Fault current circuit breaker |
Mounting type | Top-hat rail |
number of poles | 4 |
Tripping characteristic | A |
Rated current | 40 A |
Rated voltage | 400 V |
voltage type | AC |
Insulation voltage (Ui) | 500 V |
Residual current | 0.03 A |
Protection type (IP code) | IP20 |
Country of origin | Portugal |
CO₂ emissions | 17.29 kg |
Climate contribution | CHF 0.42 |
Items per sales unit | 1 pcs. |
Length | 72 mm |
Height | 72 mm |
Length | 10 cm |
Width | 8 cm |
Height | 7 cm |
Weight | 330 g |
Compare products
Goes with
Reviews & Ratings
Warranty score
How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?
Source: Digitec Galaxus- GewissNot enough data
- 1.Brennenstuhl0 %
- 1.Eaton0 %
- 1.Max Hauri0 %
- 1.Schneider Electric0 %
Warranty case duration
How many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?
Source: Digitec Galaxus- GewissNot enough data
- 1.Hager0 days
- ABBNot enough data
- BrennenstuhlNot enough data
- EatonNot enough data
Return rate
How often is a product of this brand in the «Residual-current device» category returned?
Source: Digitec Galaxus- GewissNot enough data
- 1.Max Hauri0.3 %
- 2.Steffen0.8 %
- 3.Schneider Electric1.5 %
- 4.Eaton2.7 %