Schneider Electric Over- or undervoltage between phases

Delivered between 10.2.2027 and 27.2.2027More than 10 items ordered
free shipping

Input voltage3

In Detail

Monitoring applications: Voltage
Supply voltage: 208 → 480 V ac
Contact arrangement: 1-pole switch
Electrical phases: 3
Voltage measurement range: 183 → 528 V ac
Delay time: 0.3 → 30 s
Maximum voltage detected: 528 V ac

UL, CSA, GL, C-Tick, GOST. NF EN 60255-6 and IEC 60255-6. RM17 UB3 and RM35 UB3 three-phase voltage monitors. Schneider Electric RM17/35 UB measuring and control relays for three-phase power supply monitor the correct sequence of phases L1, L2, and L3. It also monitors total failure of one or more phases, asymmetry, and over- or undervoltage with independent settings. In the event of a voltage fault, the relay opens after the user-defined delay time. If the device is powered on with a detected fault, the relay remains open. The relay opens immediately in case of a neutral conductor failure or phase loss. It checks its own power supply. Transparent front panel with hinges. Potentiometer selects voltages between phases. LED display of output status. DIN rail mounting.

30-day right of return
24 Months Warranty (Bring-in)

Compare products

Goes with