Product details
Only calibrated meters are approved for electricity billing according to §25 of the German Calibration Act. Non-compliance is an administrative offense under §19. Maximum current is 32A, with a standby loss of only 0.4 watts. This is a modular device for mounting on a DIN-EN 60715 TH35 rail. 1 division unit = 18mm wide, 58mm deep. Accuracy class B (1%). Equipped with an S0 interface. This alternating current meter measures active energy based on the current flowing between the input and output. The self-consumption of only a maximum of 0.4 watts of active power is not measured or displayed. One external conductor can be connected with a current of up to 32A. The starting current is 20mA. For expected loads exceeding 50%, a ventilation distance of 1/2 division unit must be maintained from adjacent devices. If necessary, use the spacer DS12. Two N terminals for safe cross-wiring of multiple meters. The 7-segment LC display can also be shown twice within two seconds without power supply.