Question about Powerwalker VI 2200 RLE

Avatar

1 year ago

I have 2 questions: - Why does this UPS not have a network connection? How can I manage monitoring/alerting with this UPS? For example, I would like my server to shut down or I would like to receive an e-mail or SMS. But without a network port, isn't that possible? - How is the operating time at full load calculated here? From my school physics days: - Energy (Wh) = capacity (Ah) x battery voltage (V), i.e. 9Ah x 12V = 108Wh - Running time = energy (Wh) / load/output power (W), i.e. 108Wh / 1320W = 0.08h = 4.91min and not just 1.1min as stated above. Where is my miscalculation?

Avatar
Avatar

1 year ago • purchased this product

purchased this product
Two, the autonomy time changes greatly with load. Soon mistake is that you calculate with 100% efficiency. But efficiency is load-dependent. And poor at full load. If you use the UPS with a low load, it is much higher. Therefore, the autonomy time increases more than linearly when you have less load.
Avatar

1 year ago • purchased this product

purchased this product
1) There is an optional network module that can also do SNMP. Works perfectly.
Connected to a computer or NAS via USB, it can be shut down using software. NAS usually already have this integrated, on a PC/server there is software for this. Basically, this is not a problem.
Avatar

1 year ago • purchased this product

purchased this product
Question 1: The device has a USB port. It can be monitored in this way.